Water treatment plant BOQ: every part, every fitting

Pick reverse osmosis, ultrafiltration or seawater desalination and a capacity from 125 to 50,000 litres per hour. You get the full bill of quantities: pumps, membranes, filters, dosing, instruments, control panel, cleaning, storage and every pipe, valve and fitting by size.

No water test yet? Use the defaults, then repeat with your lab results. Open the full project planner

Questions about water treatment plant parts

What parts are in a reverse osmosis water treatment plant?

A complete RO plant has 12 groups of parts: raw-water tank and feed pump; sand (multimedia) and carbon filters, plus a softener where water is hard; antiscalant dosing; a 5 micron cartridge filter; the high-pressure pump, membranes and pressure vessels; flow meters, pressure gauges and a conductivity monitor; the control panel; cleaning (CIP) equipment; UV and treated-water storage; and all the pipes, valves and fittings that join them. The planner above lists every one with sizes and quantities.

How many membranes does a 1000 LPH RO plant need?

For borehole water around 1,500 mg/L TDS, a 1,000 litres per hour plant needs about 6 x 4040 membranes in 3 pressure vessels, a 1.5 kW high-pressure pump and runs at about 70% recovery. A 10,000 L/h industrial plant uses about 12 x 8040 membranes in 2 vessels with an 11 kW pump.

What is the difference between RO and UF water purification?

Ultrafiltration (UF) removes dirt, bacteria and cloudiness but does not remove dissolved salts, so it suits county or municipal water and low-TDS boreholes. Reverse osmosis (RO) removes salts, fluoride and most dissolved minerals, so it is needed for salty or high-TDS borehole water. Use RO when TDS is above about 500-700 mg/L or the water tastes salty.

How much power does a seawater desalination plant use?

Seawater RO needs about 55-65 bar. A 1,000 L/h seawater unit has about 14.4 kW of connected load. From about 5 m3/h an energy recovery device (pressure exchanger) is standard: a 10,000 L/h plant uses a 30 kW high-pressure pump plus booster pump, about 50.2 kW connected in total.

Do I need a water softener before an RO plant?

Only if the water is hard. With hardness up to about 300 mg/L, antiscalant dosing normally protects the membranes. Above that, or with very salty water, a softener before the RO reduces scaling. The BOQ marks the softener as optional or required from the hardness you enter.

What size pipes and fittings does a water treatment plant need?

Pipe size follows the flow. A 1,000 L/h RO plant uses about 3/4" feed pipe, 1/2" permeate pipe and 1" stainless high-pressure line; a 10,000 L/h plant uses 2-1/2" feed and 2-1/2" high-pressure pipe. The BOQ counts every elbow, union, valve, tee and clip by size.