Motor Starters Compared: DOL, Star-Delta, Soft Starter and VFD

Herritech engineering teamUpdated 18 November 20264 min read

Motor Starters Compared: DOL, Star-Delta, Soft Starter and VFD
Pictured: POWER-UK ELECTRIC MOTOR 7.5HP (High speed) and POWER-UK ELECTRIC MOTOR 10HP (Low speed).
Quick answer: A DOL (direct-on-line) starter connects the motor straight to full voltage: simple and cheap, but the starting current can be about 6–8 times full-load current, so it suits small motors. A star-delta starter starts the motor in star (about a third of the DOL starting current and torque) and then switches to delta: common for medium three-phase motors with light starting loads. A soft starter ramps the voltage smoothly to cut current and mechanical shock. A VFD gives the gentlest start plus speed control.
Key facts
  • DOL: small motors, high inrush
  • Star-delta: about 1/3 starting current
  • Soft starter: smooth ramp
  • VFD: smoothest + speed control
On this page
  1. Why Starting Method Matters
  2. The Four Options Compared
  3. How a Star-Delta Starter Works
  4. Which Starter Should You Use?
  5. Motors at H-TECH
  6. Testing and Common Faults
  7. Mistakes to Avoid
  8. Frequently asked questions

Why Starting Method Matters

When an AC motor starts, it draws a large inrush current. On a weak supply or a generator, this dips voltage for everything else, trips breakers and stresses the motor, couplings and pipes (water hammer in pumps). The starter you choose controls that first few seconds.

The Four Options Compared

DOLStar-deltaSoft starterVFD
Starting currentHigh (about 6–8 × FLA)About 1/3 of DOLAdjustable, reducedLowest, near rated current
Starting torqueFullAbout 1/3 of DOLReduced, adjustableControlled, high at low speed
Speed controlNoNoNoYes
CostLowestLow–mediumMediumHighest
Typical useSmall motorsMedium motors, light start (pumps, fans)Pumps, compressors, conveyorsVariable demand, energy saving

How a Star-Delta Starter Works

  1. The main contactor and the star contactor close: the windings are connected in star, so each sees reduced voltage.
  2. The motor accelerates for a few seconds, set on a timer.
  3. The star contactor opens and the delta contactor closes: the motor now runs at full voltage.
  4. An overload relay protects against sustained over-current.

The motor must be rated for delta at your supply voltage (for example 415 V delta) and have six terminals brought out. Star-delta suits loads that start light, like centrifugal pumps and fans; heavy-start loads may stall in star.

Safety: motor starters, drives, cables, breakers and three-phase connections must be designed, installed and tested by a qualified electrician. Isolate and lock off power before touching any terminal. These figures help you plan and ask the right questions.

Which Starter Should You Use?

Motors at H-TECH

Current listed prices incl. VAT (updated 18 November 2026).

Speed control in depth: VFD guide. Motor basics: single-phase vs three-phase motors.

Testing and Common Faults

SymptomCheck
Motor hums in star, will not speed upLoad too heavy for star start; low voltage; one phase missing
Trips on changeover to deltaTimer too short; wrong wiring sequence
Overload trips after runningOverload set wrong; motor overloaded; voltage imbalance
Contactor chatterLow control voltage; worn coil

Mistakes to Avoid

Frequently asked questions

What is the difference between DOL and star-delta?

DOL connects full voltage at once with high starting current; star-delta starts in star at reduced voltage (about a third of the current) and then switches to delta.

Which is better, soft starter or star-delta?

A soft starter gives a smoother, adjustable start and soft stop; star-delta is cheaper but has a current spike at changeover.

Is a VFD better than a soft starter?

A VFD also controls speed and saves energy on pumps and fans; a soft starter only controls starting and stopping.

What size motor needs a star-delta starter?

It depends on the supply and the utility’s rules; medium three-phase motors with light starting loads are typical candidates.

How do I test a star-delta starter with a multimeter?

With power isolated, check contactor coils and contacts for continuity and the motor windings for balanced resistance; live tests should be done by an electrician.